Commercial / Multi / Industrial · BP125096
Construction of an MRI addition and ancillary spaces, (NRGH), Acute Care Hospital, B-2 occupancy, 99.8m2 additional area. Work includes moving existing link corridor and addition of interior space where existing outdoor courtyards are. Courtyards are reduced in size. To re-establish a 1 hr fire compartment at MRI area a rated double swing door on mag-hold will be added, some new walls have a 2 hr FRR. Addition of 2 sinks, MRI rooms, new corridor. 2 hr fire resistance rating required for floor and supports. Alternative Solution water curtain at windows in link corridor & MRI room for exit exposure protection by Celerity. Revision: July2019 CRP & Architect changed. Dec. 2019 Revision: Fire Suppression Eng changed. Building Classification : BCBC2012 - 3.2.2.38 /3.2.6, non combustible construction, sprinklered with fire alarm. Major occupancy B-2 with subsidiary occupancies. Existing Alternative Solution for exit exposure & heavy timber by GBA Aug 12, 2010
Other addresses listed in this application: 1200 DUFFERIN CRESCENT.
Source: City of Nanaimo — Planning, building, demolition and subdivision records.