Troubleshooting flickering, lights flickering, fridge going in and out off loss of power mode has been getting progressively worse Everything with fluctuating voltage is on L2 switch several branch circuits to L1 and solves problems.
Troubleshooting flickering, lights flickering, fridge going in and out off loss of power mode has been getting progressively worse Everything with fluctuating voltage is on L2 switch several branch circuits to L1 and solves problems. Open 100A fused Service disconnect meter line side before fuse after meter 117V on L1 107V on L2 Duplex Dwelling Unit 320 read 117 on L1 117 on L2 Problem volt drop happens on L2 before service disconnect. Will call Hydro after receiving permit number