heat pump installation. did a load calculation with addition of new heat pump, which results in a total load of just over 110A on their 200A FP panel ran power for 25A heat pump using 10/2 romex, junctioned to 10/2 teck in crawl space. - 1/2” liquid tight whip run from disco - surge protector connected in parallel with line side Used proper wet connect for teck wire at disco - deleted old furnace feed and tied through their on demand hot water system to a receptacle from old furnace switch. -proper voltage was measured at the disco as was the panel schedule to reflect the new heat pump and deletion of furnace.