Building permit — Addition / Alteration · DB-2025-00541
Field Review - Addition / Alteration - Interior alterations to change the use from Retail shell space at 1119 Kingsway to Fitness Centre (Low occupant load A2 – group D) on the ground floor of this mixed-use building on this site. Schedule A/Schedule B Architectural - Jaesung Jung (604) 842-6280 Schedule B Mechanical/Plumbing - Satwik Shetty, P.Eng (778)-360-2153 Schedule B Structural - Dragan Todorovic, P. Eng (604)-264-1450 A separate sprinkler permit may be required, to be determined by the district building inspector 3.1.2.6 (Low occupant A2 – Group D) - Suite is separated from the remainder of the building by a fire separation having a fire-resistance rating of not less than 1 hr. and FRR is waived if the building is sprinklered. - A permanent sign, with lettering not less than 50 mm high with a 12 mm stroke, indicating the occupant load for the suite 25 persons, shall be posted in a conspicuous location near the suite’s principal entrance. Ok for field review per J.Zhang
Source: Vancouver — Issued permits — 2023-2025. Contains information licensed under the Open Government Licence – Vancouver.